Glossary

VLF Cable Testing

VLF cable testing uses a very low frequency AC voltage, typically 0.1 Hz or lower, to test the insulation of power cables on site. At that frequency the test equipment can be much smaller and lighter than a 50 Hz test system, which makes it practical for cables with a high capacitance.

Why use a very low frequency?

A long cable behaves like a large capacitor. Charging it at 50 Hz takes a lot of power and heavy equipment, while at 0.1 Hz the required current is about 500 times lower. That is why VLF test sets are portable enough to bring to site.

Withstand and diagnostic tests

A VLF set is mainly used for withstand testing after installation or repair, where the cable has to hold a defined voltage for a defined time. The same source can also drive diagnostics such as tan delta and partial discharge measurements. Guidance such as IEEE 400.2 describes VLF field testing of shielded power cable systems; the applicable requirement is confirmed per project.

The B2 HVA120 VLF test set

  • VLF sine wave output up to 120 kV peak (85 kV RMS) at 0.01 to 0.1 Hz
  • Output load of 0.5 µF at 0.1 Hz and 85 kV RMS
  • VLF square wave up to 100 kV and DC output up to ±100 kV
  • Sheath test up to 10 kV with negative polarity
  • Reference: medium-voltage cables up to 69 kV according to IEEE 400.2
  • Supplied with HV test lead, grounding cable, reverse voltage protection, dual discharge device and a calibration certificate

Is it suitable for your cable?

Suitability depends on the cable voltage, length and capacitance, the test standard and the objective. Share the cable type, voltage level, route length, test objective, applicable standard, location and planning window so Reynard can confirm the unit.

Frequently asked questions

Is the HVA120 suitable for every cable test?

No. Suitability depends on the cable voltage, length, capacitance, test standard and project objective. Reynard reviews this before confirming the unit.

Can Reynard provide high-voltage testing specialists?

Yes. The rental request can include Reynard test engineers for preparation, test execution, safety control and reporting.

Reynard

Reynard designs, implements and maintains high-end technological and sustainable connections and terminations for the Renewable Energy sector. Reynard belongs to the market leaders in the field of on and offshore cable connectivity.

More glossary terms

Tan Delta Testing

Tan delta testing measures dielectric losses in cable insulation to assess its condition. Learn how it works, what it shows and when to rent a tan delta set.

Read definition

Electric Capstan

An electric capstan pulls cable with steady, controlled force using a rope wrapped around a motor-driven drum. Learn how it works and when to rent one.

Read definition
View glossary