Tan delta testing, also called dissipation factor testing, measures the dielectric losses in the insulation of a cable. The tan delta value rises as the insulation ages or degrades, so the test indicates the condition of the whole cable length without damaging it.

How tan delta testing works

A test voltage is applied to the cable and the ratio between the resistive and the capacitive current is measured. In healthy insulation that ratio is small and stable. Ageing, moisture ingress or water trees in XLPE insulation increase the losses, so tan delta rises, especially at higher voltage steps.

What the results show

Measurements are usually taken at several voltage levels and compared with reference values or earlier results, following the applicable standard or client requirement. The outcome supports maintenance decisions: can the cable stay in service, does it need closer monitoring, or should it be repaired or replaced? A partial discharge measurement can be added to help locate defects.

Tan delta and VLF testing

Tan delta testing is a diagnostic method and not the same as a VLF withstand test. A withstand test checks that the cable survives a defined voltage; tan delta assesses the condition of the insulation. The two can be used alongside each other depending on the objective. A VLF source is often used to energise the cable for a tan delta measurement.

The TD120-MC (85 kVrms)

The rental set is the TD120-MC tan delta diagnostics system with a voltage reference of 85 kVrms. A related partial discharge diagnostic system (PDTD120-2, 120 kV) can be discussed as part of the same diagnostic request where applicable.

Frequently asked questions

Is tan delta testing the same as VLF testing?

No. Tan delta is a diagnostic method; VLF describes the very low frequency voltage source used for testing. Tan delta can be measured with a VLF source, but a VLF withstand test is a different test.

Can Reynard perform the tan delta test?

Yes. The rental request can include Reynard test specialists for setup, measurement and reporting.

Reynard

Reynard designs, implements and maintains high-end technological and sustainable connections and terminations for the Renewable Energy sector. Reynard belongs to the market leaders in the field of on and offshore cable connectivity.

More glossary terms

VLF Cable Testing

VLF cable testing uses a very low frequency AC voltage (0.01 to 0.1 Hz) to test cables on site. Learn how it works, which standards apply and when to rent.

Read definition

Electric Capstan

An electric capstan pulls cable with steady, controlled force using a rope wrapped around a motor-driven drum. Learn how it works and when to rent one.

Read definition
View glossary