Insulation resistance testing applies a DC test voltage to the insulation of a cable or other asset and measures how strongly the insulation resists current flow. A high, stable resistance indicates sound insulation; a low or falling value points to moisture, contamination or ageing.
How an insulation resistance test works
The tester applies a chosen DC voltage and reads the resulting leakage current, which it converts into a resistance in megaohms, gigaohms or teraohms. The higher the test voltage, the more demanding the test, so the voltage is chosen to match the rating of the asset.
PI, DAR and other test modes
Beyond a single spot reading, advanced testers run extended measurements that show how the insulation behaves over time:
- Polarisation index (PI): the ratio between the resistance after 10 minutes and after 1 minute
- Dielectric absorption ratio (DAR): a similar ratio over a shorter time
- Dielectric discharge (DD), step voltage (SV) and ramp tests for deeper insight
The Megger S1-1568/2-EU EXPERT 15 kV
The rental tester covers test voltages from 250 V up to 15 kV and measures up to 35 TΩ. It runs on mains or a rechargeable battery and supports insulation resistance, PI, DAR, DD, SV and ramp testing.
What to prepare for a request
Share the asset type, voltage level, test objective, location, planning window and whether you need an operator or test engineer. Accessories, documentation and support needs vary per test scope, so Reynard confirms the package before rental.
Frequently asked questions
What is the difference between PI and DAR?
Both compare insulation resistance at two moments in a test. PI uses 10 minutes against 1 minute, DAR uses a shorter interval. A low value for either points to moisture, contamination or degraded insulation.